PRODUCT

Sprinkler Head

제품사진

AUG68-M80-SSP

Product overview
Glass bulb sprinkler with Frame Type Head assembled. The thermal part of the glass bulb is filled with thermal expansion liquid in a special glass, and it is the best head for an exposed piping type without a ceiling like parking lot. The fire sprinkler contractor, Kwang Woon's Glass bulb type sprinkler head uses safety bulb made by Job, Germany, the world's largest glass bulb maker that does not cause malfunctions in a compact and lightweight structure, and ensures safety and sufficient reliability. * Residential Fire Sprinkler Head * Liquid Inside Sprinkler Bulb * Glass Bulb Sprinkler * Bulb Type Sprinkler
    Notice: Undefined offset: 20 in /home/kwangun/public_html/html/_module/product/view.html on line 29
Product Specifiaction
  • glassbulb img
  • Connection thread : General standard PT 1/2"(15A)
  • Operating pressure range : 0.15 ~ 1.2 MPa
  • Hydrostatic test pressure : 2.5 MPa / 5 min
  • Thermostat characteristics : Glass bulb
  • O perating temperature classification : 68 ℃ - Red / 93 ℃ - Green
  • Distribution of water direction : : Upward (SSU sprinkler head) / Downward (SSP sprinkler head) / Horizontal (SSH), Dry sidewall sprinkler
  • Sensitivity characteristics Classification : Standard response type (SR) / Early response type (QR)
Production list
Item No. Display
Temperature
Sensitivity Characteristic Effective Watering Radius Effective Watering Radius Connection Thread Watering Quantity
AG68-M80-SSU 68℃ Standard response type

Upward

SSU sprinkler head

r 2.3 PT 1/2” 80LPM
AG68-M80-SSP 68℃ Standard response type

Downward

SSP sprinkler head

r 2.3
AG93-M80-SSU 93℃ Standard response type Upward

SSU sprinkler head

r 2.3
AG93-M80-SSP 93℃ Standard response type

Downward

SSP sprinkler head

r 2.3
AG68-Q80-SSU 68℃ Early response type Upward

SSU sprinkler head

r 2.3
AG68-Q80-SSP 68℃ Early response type

Downward

SSP sprinkler head

r 2.3
AG68-M80-SSH 68℃ Standard response type Standard Sidewall type spraying
AG93-M80-SSH 93℃ Standard response type
AG68-Q80-SSH 68℃ Early response type
AG93-Q80-SSH 93℃ Early response type
AGOP-80-SSU Open type - Upward

SSU sprinkler head

r 2.3
AGOP-80-SSP Open type -

Downward

SSP sprinkler head

r 2.3
AUG68, 93-M80-SSU 68, 93℃ Standard response type Upward

SSU sprinkler head

UL 199 NPT1/2 K5.6
AUG68, 93-M80-SSP 68, 93℃ Standard response type Downward

SSP sprinkler head